Air humidity (operation) |
10% to 95%, non-condensing as per DIN EN 61131-2 |
Air humidity (storage) |
10% to 95%, non-condensing as per DIN EN 61131-2 |
Air humidity (transport) |
10% to 95%, non-condensing as per DIN EN 61131-2 |
Air pressure (operation) |
≥ 795 hPa (height ≤ 2000 m) as per DIN EN 61131-2 |
Air pressure (storage) |
1013 hPa (height 0 m) to 700 hPa (height 3000 m) as per DIN EN 61131-2 |
Air pressure (transport) |
1013 hPa (height 0 m) to 700 hPa (height 3000 m) as per DIN EN 61131-2 |
Pollution severity |
2 |
Rail |
TS 35 |
Restricted area |
Type of restricted area |
thermal |
Negative expansion |
Y coordinate |
-40 mm |
Z coordinate |
0 mm |
X coordinate |
-28 mm |
|
Positive expansion |
X coordinate |
43 mm |
Z coordinate |
85 mm |
Y coordinate |
160 mm |
|
|
|
Shock |
15 g over 11 ms, half sinus wave, acc. to IEC 60068-2-27 |
Surge voltage category |
II |
Test voltage |
500 V |
Vibration resistance |
5 Hz ≤ f ≤ 8.4 Hz: 3.5-mm amplitude as per IEC 60068-2-6, 8.4 Hz ≤ f ≤ 150 Hz: 1 g acceleration as per IEC 60068-2-6 |
UR20-4DO-PN-2A